Details
The Hansen refrigerant liquid level float switch (HLL Series) is used to electrically indicate or control a liquid level by opening and closing a SPDT switch. It may be used to control a liquid level by opening and closing a liquid feel solenoid valve or similar device. It may also serve as a high or low level alarm or cutout. A standard 2" differential prevents the switch from "short cycling" due to fluctuations of the liquid level; closer differentials are available to 1/2".
Features:
- Rugged 10 Ampere switching capacity eliminates most switch burnouts due to overloads.
- Spring at top and bottom of float chamber prevent float ball damage caused by gas surges
- High strength larger diameter ball stem eliminates potential stem bending or breakage
- Simple, direct, switch pivot-arm overcomes potential mechanical failure.
- Hermetic Switch housing assembly with optional metal cover
- Optional switch housing heater for applications below -20°F.
- Switch Assembly and/or tank assembly are interchangeable with the R/S LL series float switches.
More Information
- Weight: 15.000000
- Condition: New
- Brand: Hansen
- Safe Working Pressure: 400 PSIG
- Operating Temperature: -50°F to 150°F
- Width: 7.0000
- Height: 6.0000
- Depth: 25.0000